The main transformer differential protection action trip is due to:
(1) A short circuit fault has occurred in the main transformer and its bushing lead-out line.
(2) Protect the secondary line from malfunction.
(3) The current transformer is shorted or open.
(4) Internal fault of the main transformer.
The principle of processing is:
(1) Check the external bushings and leads of the main transformer for faults and abnormalities.
(2) If the abnormality is not found after the inspection in item (1), but the station has a DC unstable grounding hazard or has been operated with DC grounding, consider whether there is a DC two-point earthing fault. If so, the short-circuit point should be eliminated in time and the transformer should be re-powered.
(3) If the inspection of item (2) is carried out, no DC ground fault is found, but there is voltage at both ends of the outlet intermediate relay coil, and the grounding of the differential relay has returned, it may be the differential trip circuit and the protection secondary line short circuit. As a result, the short-circuit point should be eliminated in time, and then the power is sent.
(4) Check whether the high and low voltage current transformers have open circuit or poor terminal contact, find the problem in time, and then resume power transmission to the transformer.
(5) If the above check does not find any fault or abnormality, it can be judged as the internal fault of the transformer, stop the operation, wait for the test, if it is the lead line fault, replace the lead wire in time.
(6) If the differential protection and the gas protection trip at the same time, it should first be judged as the internal fault of the transformer and treated according to the heavy gas protection action.

Camera Watch

An electronic clock device with a wireless network monitoring camera is characterized in that it comprises an electronic clock device body with a wireless network monitoring camera; the electronic clock device body with a wireless network monitoring camera is composed of a foot, a wireless transmission module, a It consists of a rechargeable battery, a speaker, a touch display screen, a camera, a casing, an infrared device, and a microprocessor; the feet are fixedly installed at the bottom of the rechargeable battery; a casing is fixedly installed on the top of the rechargeable battery, and the The interior is provided with a touch screen, a camera, an infrared device and a microprocessor; the microprocessor is electrically connected to the rechargeable battery through wires; the wireless transmission module, speaker, display, camera and infrared device are connected to the micro processor through wires The display screen is arranged at the bottom of the camera, and the camera is surrounded by an infrared device; the wireless transmission module is fixedly installed on both sides of the rechargeable battery, and the speakers are opened on both sides of the casing